AAAC Conductor-All Aluminum Alloy Conductor

Application: Used as bare overhead conductor for primary and secondary distribution. Designed for utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.

AAAC Conductor Feature

(1)AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.
(2)The aluminum alloy conductors are used in replace of single-layer ACSR conductors to reduce power loss in overhead distribution and transmission lines,when replacing the aluminum conductor steel reinforced , the AAAC can save 5-8% of the construction cost.
(3)AAAC referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to replace the conventional ACSR.

 IEC Standard AAAC Condcutor Parameter Date

Code number Area Number of wires Diameter Linear mass Rated strength
mm2 Wire(mm) Cond(mm) kg/km kN
16 18.6 7 1.84 5.52 50.8 6.04
25 29 7 2.3 6.9 79.5 9.44
40 46.5 7 2.91 8.72 127.1 15.1
63 73.2 7 3.65 10.9 200.2 23.06
100 116 19 2.79 14 319.3 37.76
125 145 19 3.12 15.6 399.2 47.2
160 186 19 3.53 17.6 511 58.56
200 232 19 3.95 19.7 638.7 73.2
250 290 19 4.41 22.1 798.4 91.5
315 366 37 3.55 24.8 1008.4 115.29
400 465 37 4 28 1280.5 146.4
450 523 37 4.24 29.7 1440.5 164.7
500 581 37 4.47 31.3 1600.6 183
560 651 61 3.69 33.2 1795.3 204.96