 
															Medium Voltage ABC Cable
Medium voltage typically refers to voltage levels ranging from 1 kV to 36 kV, although the exact range may vary depending on regional standards.
Share
- Conductor
 Class 2 Circular compacted stranded Aluminium
- Conductor Screen
 Extruded semi-conductive layer
- Insulation
 XLPE (Cross-linked polyethylene)
- Insulation Screen
 Extruded semi-conductive layer
- Metallic Screen
 Copper wire screen or copper tape screen
- Separator
 Semi-conductive swellable tape
- Outer Sheath
 HDPE (High Density Polyethylene)
- Support Conductor
 Galvanized steel wires
- Sheath Colour
 Black

ABC cables are commonly used for distributing power in residential areas, rural regions, and areas where underground cabling is not feasible or cost-effective.
Medium voltage ABC cables offer advantages such as reduced installation time, lower maintenance requirements, and improved resistance to external factors like weather and environmental conditions.
They provide a reliable and efficient solution for power distribution in various settings.
IEC 60502-2/AS/NZS 3599-1, BS 2627.
| Cross section | No. of wires | Conductor diam. | Overall Diameter | Minimum breaking load | Approx. weight | Max. DC-resistance at 20°C | Ampacity 90°C | 
| [mm²] | 
 | [mm] | [mm] | [kgf] | [kg/km] | [Ohm/km] | [A] | 
| 35 | 7 | 7.1 | 13.6 | 464 | 190 | 0.868 | 187 | 
| 50 | 7 | 8.2 | 14.7 | 663 | 235 | 0.641 | 225 | 
| 70 | 19 | 9.7 | 16.2 | 928 | 315 | 0.443 | 282 | 
| 95 | 19 | 11.5 | 18 | 1259 | 400 | 0.32 | 345 | 
| 120 | 19 | 12.9 | 19.4 | 1591 | 500 | 0.253 | 401 | 
| 150 | 19 | 14.2 | 20.7 | 1988 | 580 | 0.206 | 456 | 
| 185 | 37 | 16.2 | 22.6 | 2452 | 695 | 0.164 | 525 | 
| 240 | 37 | 18.4 | 24.9 | 3182 | 875 | 0.125 | 625 | 


Manufacturing Process
 
															Conductor Stranding
 
															Extruded Insulation
 
															Cabling
 
															Armoured
 
															Extruded Outer Sheath
 
															Packing On Drum
 
				


